Protonest Master is an industrial IoT gateway that collects data from sensors and field devices, controls outputs, and publishes readings to an MQTT broker over Wi-Fi or cellular. You configure it through a built-in web console, so you do not need to install desktop software.
How Protonest Master works
- Collect: Read the built-in environment sensor and connected analog channels, temperature probes, contact inputs, and Modbus devices.
- Connect: Join the internet through a 2.4 GHz Wi-Fi network or a cellular SIM.
- Publish: Send each reading to your MQTT broker under a dedicated subtopic such as
environmentoranalog-inputs. - Monitor and control: Review live readings and hardware health on Overview, and control configured outputs locally or through MQTT.
Capabilities
| Area | What the gateway provides |
|---|---|
| Environment | Enclosure temperature in °C and humidity in %RH |
| Analog inputs | Four channels: Analog 1-2 for voltage and Analog 3-4 for current |
| Temperature probes | One NTC thermistor input and one PT100 precision probe input |
| Digital I/O | Three contact inputs, three digital outputs, and one relay |
| Field bus | RS-485 Modbus RTU interface |
| Internet | 2.4 GHz Wi-Fi or cellular with a SIM |
| Cloud | MQTT publishing with optional TLS and certificate authentication |
| Power | 7-36 V DC external power with battery backup |
Each channel can be enabled independently. A channel that is not enabled appears as Disabled on the Overview page.
What you need
Before you begin, prepare:
- A laptop, tablet, or phone with Wi-Fi and a web browser.
- A 7-36 V DC power supply; 12 V is recommended.
- The setup-hotspot password printed on the gateway label.
- Both supplied antennas, fitted to their connectors and tightened by hand.
- For Wi-Fi, the name and password of a 2.4 GHz network. The gateway does not support 5 GHz Wi-Fi.
- For cellular, an installed and activated SIM plus the APN from your provider.
- Your MQTT broker address, port, client ID, and authentication details.
- The datasheets and wiring details for every sensor or field device you intend to connect.
Front-panel LEDs
| LED | Normal indication |
|---|---|
| CHARGING | Battery connected |
| ACTIVITY | Activity, or a repeating diagnostic blink code |
| RELAY | Relay switched on |
| POWER | External power present |
| STATUS | On when the gateway is working normally |
| NETWORK | Cellular modem connected |
Activity LED error codes
When STATUS turns off and ACTIVITY repeats a blink pattern, count the blinks between pauses.
| Pattern | Meaning | What to do |
|---|---|---|
| 1 blink | A hardware module was not detected | Check that plugs and internal connections are fitted, then open Diagnostics > Hardware. |
| 2 blinks | The gateway could not initialize | Restart it and check the power supply and polarity. |
| 3 blinks | A configuration could not be applied | Check saved settings, especially the 2.4 GHz Wi-Fi name and password. |
| 4 blinks | A runtime or connectivity operation failed | Check the internet connection and MQTT settings, then review Diagnostics > Logs. |
Documentation map
Start here
Quick start
Connect to the setup hotspot, complete onboarding, and verify the dashboard.
Configure
Sensors and I/O
Set up sensor channels, digital inputs and outputs, and Modbus values.
Connect
Network connection
Connect the gateway through Wi-Fi or cellular.
Publish
MQTT broker
Configure broker security, delivery behavior, and publish topics.
Navigate
Web console
Understand the menu, status indicators, dashboard, and save behavior.
Maintain
Firmware and diagnostics
Install firmware updates and inspect hardware, logs, tasks, and crash reports.
Administer
Device settings
Update device identity, administrator credentials, and the setup hotspot.
Recover
Defaults and troubleshooting
Review factory defaults, recover common faults, reset safely, and contact support.